ACSON Air Conditioner Error Codes


Error Codes for Wall-Mounted Inverter Units

Error codes are displayed as indicated below, accompanied by a long beep.

Error Codes and Solutions

Error CodeSolution
E1Loose/short-circuited ambient air sensor contact. Check the room sensor connection/replace the room sensor.
E2Open indoor coil sensor contact. Check the indoor coil sensor connection/replace the indoor coil sensor.
E3Open outdoor coil sensor contact. Check the outdoor coil sensor connection/replace the outdoor coil sensor.
E4Compressor overload protection/indoor or outdoor coil sensor short-circuited. If running amperage is too high, replace the compressor; otherwise, replace the coil sensor.
E5Gas leakage. Check for leaks, repair, and recharge refrigerant.
E6Pump failure. Clear blockages in the drainage pipe. If the pump is not working, replace it.
E7Outdoor coil sensor present (MS model). Remove the outdoor coil sensor.
E8Hardware error (touch switch pin short-circuited). Check the condition of the touch switch pin.
E9No feedback from the indoor fan. Check the indoor fan motor/its wiring.
EEEEPROM defrosting.

Error Codes for G18 and GS02 – Inverter Models

Error CodeIssue
00Normal operation.
U0Insufficient gas.
U2DC voltage out of range.
U4Communication error.
U7Signal transmission error (on outdoor unit PCB).
UAInstallation error.
UFCommunication error (indoor and outdoor), piping, or wiring issue.
OHAnti-freeze function active in another room.
A1Indoor PCB error.
A3Water pump error.
A5Anti-freeze activation.
A6Abnormal indoor fan motor.
C4Indoor heat exchanger thermistor short/open.
C9Indoor ambient thermistor short/open.
E1Outdoor PCB error.
E3High-pressure protection.
E4Low-pressure protection.
E5Compressor motor lock.
E6Compressor startup error.
E7Outdoor DC fan motor lock.

Multi-Compressors with Sequential Controller

Error CodeIssue
E01Manual reset required (possible causes).
E02Compressor 1 high temperature (overload).
E03Compressor 2 high temperature (overload).
E04Compressor 3 high temperature (overload).
E05Compressor 4 high temperature (overload).
E06Compressor 1 high-pressure trip/open contact.
E07Compressor 2 high-pressure trip/open contact.
E08Compressor 3 high-pressure trip/open contact.
E09Compressor 4 high-pressure trip/open contact.
E10Compressor 1 trip/low refrigerant level/abnormal outdoor unit.
E11Compressor 2 trip/low refrigerant level/abnormal outdoor unit.
E12Compressor 3 trip/low refrigerant level/abnormal outdoor unit.
E13Compressor 4 trip/low refrigerant level/abnormal outdoor unit.
E14Room sensor short-circuited.
E15Room sensor open.

Error Diagnosis via Wired Controller

Error CodeMeaning
F3Broken sensor (indoor outlet coil).
F4Broken sensor (indoor return air).
F5Broken sensor (indoor supply air).
F6Communication failure between indoor unit and controller.
F7Ambient temperature exceeds the limit.
F84WV malfunction.
F9Refrigerant leakage.
FAController storage failure.
FCIndoor and outdoor communication failure.

R410A Multi-Digital Scroll System (MDS-B Series)

Error CodeMeaning
EC0000## indoor unit communication.
EC0101# indoor unit communication failure.
ER48Digital compressor overload.
ER49Fix 1 compressor overload.
ER50Fix 2 compressor overload.
ER51Fix 3 compressor overload.
ER52Discharge pressure too high.
ER53Suction pressure too low.
ER54Outdoor unit IC error.
ER55System error.