The Toshiba Air Conditioner Error Codes help technicians and users identify and resolve potential issues efficiently.


Error Codes and Solutions

Error CodeSolution
E01No communication between the remote control and the indoor unit.
E02Local controller failure: unable to transmit.
E03The master indoor unit does not receive data from A-B.
E04The indoor unit (excluding the dual slave) does not receive communications from the outdoor unit; may also involve the klixon on the discharge pipe of the outdoor unit.
E08Duplicate indoor unit address.
E09Two local controllers connected in a group, both set as masters.
E10Failure of the indoor unit PSB.
E18Communication failure between the master indoor unit and the slave indoor unit(s).
F01Error with the TCJ sensor (liquid) in the indoor unit (open or closed circuit: resistance measured in kΩ).
F02Error with the TC2 sensor (vapor) in the indoor unit (open or closed circuit: resistance measured in kΩ).
F04Error with the TD sensor (discharge) in the outdoor unit (open or closed circuit: resistance measured in kΩ).
F06Error with the TE sensor (coil) in the outdoor unit (open or closed circuit: resistance measured in kΩ).
F08Error with the TO sensor (ambient) in the outdoor unit (open or closed circuit: resistance measured in kΩ).
F10Error with the TA sensor (return air) in the indoor unit (open or closed circuit: resistance measured in kΩ).
F29Indoor unit PCB failure.
H01Excessive current detected in the outdoor unit inverter compressor.
H02Excessive current detected in the master outdoor unit shortly after startup.
H03Current detected in the master outdoor unit while in standby mode.
H06Low pressure detected in the outdoor unit by the Ps sensor (0.2 bar – 2.9 psig).
L03Duplicate master indoor units in a group.
L07Indoor unit in a group previously addressed as a single unit: check the address.
L08Indoor unit addresses not set: check the address.
L09Indoor unit capacities not set (check DN 11 code).
L29IPDU error in the outdoor unit (reduction in the number of detected IPDUs).
L30Input on the CN80 circuit of the indoor PCB for 1 minute.
L31Outdoor unit PCB error.
P01Error with the indoor unit fan motor.
P03High discharge temperature in the outdoor unit (TD1 exceeds 115°C).
P04Outdoor unit high-pressure switch activated (detected by high temperature on the TE sensor in digital/super digital inverter units).
P07Overheating of the outdoor unit PCB heat sink (temperature exceeds 90°C).
P10Float switch in the indoor unit activated.
P12Indoor unit fan motor error detected by the feedback circuit.
P19Incorrect temperature change registered (four-way valve error).
P22IPDU error in the outdoor unit fan motor.
P26Short circuit in the outdoor unit’s giant transistor.
P29Compressor error in the outdoor unit detected by the feedback circuit.
P30Error in the follower unit of the indoor group control/duplicate central control addresses.
P31Indoor unit PCB error.
C05Transmission error in the TCC-Link central control device.
C06Reception error in the TCC-Link central control device.